TECHNICAL TYPICAL PROPERTIES OF COMMERCIAL LPG GRADES |
Commercial Propane |
Commercial Butane |
|
Gas: Air ratio for combustion |
1:24 |
1:30 |
|
Flame temperature in air max. *C |
1930 |
1900 |
|
Flame Speed cm/sec |
44 |
44 |
|
Relative Density of liquid at 15.6*C (Water at 0*C = 1.0) |
0.51 |
0.58 |
|
Litre/tonne at 15.6*C |
1975 |
1742 |
|
Relative Density of gas at 15.6*C (Air at 15.6*C = 1.0) |
1.52 |
2.01 |
|
Volumes of gas (litres) per kg of liquid at 15.6*C |
537 |
411 |
|
Ratio gas: liquid volume at 15.6*C |
279 |
238 |
|
Boiling Point at 1 atm. *C |
-45 |
-2 |
|
Vapour Pressure-typical bar g at 0*C / 15.6*C |
3.8 / 6.4 |
0.5 / 1.6 |
|
Limits of flammability (percentage of gas by vol. In gas-air mixture) Upper / Lower |
10 / 2 |